Description
Bitmain ANTRACK V1
The Bitmain Antminer Antrack V1 is made for people who’re really into mining. It has a cooling system that uses water to keep things cool. This cooling system is really good. Can handle up to four S19 Hyd. Or S21 Hyd. Units at the time. The Bitmain Antminer Antrack V1 keeps the temperature low. The noise down which means the Bitmain Antminer Antrack V1 can mine for cryptocurrency really well even when it is using a lot of power like 24kW. The Bitmain Antminer Antrack V1 is a good choice, for serious miners because it is designed to be used in big mining operations.
Engineered for professional infrastructure, the Antrack V1 utilizes a robust 380-415V power input and a specialized water flow system to maintain optimal thermal balance across all connected units. With a sturdy 207kg frame and integrated Ethernet connectivity, this rack provides the reliable, heavy-duty foundation needed to maximize uptime and extend hardware longevity in demanding mining environments.
Specifications
| Product Glance | Value |
| Model | ANTRACK |
| Version | V1 |
| Capacity | 4 units ANTMINER (S19 Hyd./S21 Hyd. series) |
| Maximum load,kW | 24 |
| Detailed Characteristics | Value |
| Hardware Configuration | |
| Size (Length*Width*Height), mm (without package) | 1000*600*2100 |
| Size (Length*Width*Height), mm (with package) | 2260*1130*780 |
| Net weight, kg (without package) | 207 |
| Gross weight, kg (with package) | 300 |
| Network connection mode | EJ45 Ethernet 10/100M |
| Power Supply | |
| Power supply AC Input voltage, Volt(1-1) | 380~415 |
| Power supply AC Input Frequency Range, Hz | 50~60 |
| Power supply AC Input current, Amp(1-2) | 80 |
| Environment Requirements | |
| Ambient temperature, °C(1-3) | 15~45 |
| Water flow, L/min | 32.0~40.0 |
| Water pressure, bar | ≤3.5 |
| Working fluid(1-4) | Antifreeze (10%) |
| Liquid PH | 7.8~8.5 |
| Storage temperature, °C | -20~70 |
| Operation humidity(non-condensing), RH | 10~90% |
Notes:
(1-1) Caution: Wrong input voltage may probably cause miner damaged.
(1-2) Three-phase AC input.
(1-3) Please keep the ANTRACK V1’s ambient temperature between 15 °C and 45 °C. Maintain at least 1 m of clearance in front of and behind the unit, and ensure adequate room ventilation to prevent exhaust-air recirculation. Under normal operation, the miner’s inlet-water temperature will be about 5 °C above ambient. When operating with older models (e.g. S19 Hyd., T19 Hyd., S19 Pro Hyd., S19 Pro+ Hyd., T19 Pro Hyd., S19 XP Hyd.), ensure the ambient temperature does not exceed 35 °C.
(1-4) If the water conductivity is ≥100 μs/cm, the fluid must be replaced. The water conductivity is less than 20 μs/cm when the system is running at the first time.
PS: An ANTRACK unit features four rack slots, each equipped with one network cable and one power cable tailored for Hydro-cooling miners. The unit also includes a water pump, eight fans, a heat exchanger and a plate heat exchanger.
For smooth operation of the ANTRACK system, please prepare the following additional items:
• A three‑phase, five‑core 380–415 V AC power cable (6AWG)
• An Ethernet cable
• 20 L of 10 % antifreeze